6 Critical Tips For Your Emergency Lighting System


Key Points:
  • Emergency Lighting and Facility Standby Power are Required By Law.
  • Emergency Egress Paths must have a minimal average brightness of 1fc (2fc in NYC) at the floor. (NFPA 101, Section 7.9.2.1, and IBC, Section 1006.4)
  • Emergency Lighting must automatically engage in 10 seconds or less.
  • Emergency Lights and Exit Signs must operate for a minimum of 90 minutes.
  • Braille Exit Signs and Exit Route Signs are Required.
  • Fire Inspectors, Building Inspectors, and OSHA enforce regulations.
  • NFPA (National Fire Protection Association's Life Safety 101 provides guidance.
  •  

Emergency lights and exit signs are specified and installed at the time of the building's construction but are often neglected thereafter. A clear and easy-to-follow plan ought to be created and followed to ensure compliance and safety. When the Occupational Safety and Health Association (OSHA) imposes fines for non-compliant emergency lighting, it can cost up to $7,000 for a first-time violation and as much as $70,000 for a repeat violation. Besides the fines, if an emergency occurs and the system is faulty, lives may be at risk and you may face jail time. Follow these 6 Critical Tips to keep you and your building safe.

Exit Paths:

Exit paths must be clear, accessible, and adequately lit — This includes exit access (leading up to the exit), the exit itself, and the exit discharge (outside of the exit). Exit routes must also remain visible during any construction or building repairs.

Emergency Lights:

Emergency lights should turn on automatically within 10 seconds of a power outage, last for at least 1.5 hours, and provide at least 1fc average of light along the path of egress. it is also important to have emergency lights in enclosed areas, such as bathrooms, changing rooms, stairwells, corridors and lobbies, to ensure occupants can safely manage the path of egress.

Exit Signs

Exit Signs must be clearly marked and illuminated during power outages and darkness during building occupancy. The signs must remain illuminated during darkness for at least 90 minutes. You must check the batteries on exit signs once per month and do a full discharge test once per year. These are required by law. In addition to Exit Signs, you will need signage posted indicating the direction of the nearest exit, if not immediately obvious. This includes braille signs.

Clarity

If there are doors or paths along the exit route that might be mistaken for an egress path, you must post a sign that says, Not An Exit or the actual use of the room. NFPA Life Safety 101 Standards require that the exit path be clearly marked by a sign with the word “exit” that is not decorated or obstructed from sight.

Batteries

Batteries have a usable life span which can be shortened by vibrations, temperature fluctuations, and by prolonged discharge. Building code and life safety laws require that batteries be tested every 30 days and annually. Safety lighting equipment have a must-to-test button which can be used to test the battery. If you push the button and you see that the lighting doesn't engage or your hear a buzz, you must determine the cause of the failure immediately. Often, it is the battery. Take note of the dimensions, voltage, amp hours, terminal connector, and battery-type (Sealed Lead Calcium, Sealed Lead Acid, Ni-Cad, etc..)  ExitExpo.com has every type of battery, we can help you select the correct battery.

Maintenance

Periodic Inspections are required monthly, yearly, and after prolonged power outages. Proper maintenance can save lives, prevent injury, and reduce your legal exposure. Inspections include a visual check for exterior damage and a battery test. An annual inspection includes:

  1. Checking battery terminals. (tightness, corrosion, wear)
  2. Measuring the “float voltage” (the constant voltage that is applied continuously to a battery cell)
  3. Battery-load and discharge test that simulates the unit being lit on battery backup for 90 minutes.
  4. Bulbs and batteries should also be replaced as needed. *consider retrofitting incandescent or fluorescent bulbs to long-lasting LEDs

Systematic Review and Documentation

Create and maintain clear plans for inspecting and testing your equipment. Testing and maintenance requirements for emergency lighting can be found in NFPA 101, Section 7.9.3. It is recommended that you create a log book that contains the asset tag of the equipment inspected, an index of installation locations by equipment, along with a log of inspections that contain the date and time of inspections, type of inspection, who performed the inspection, recommended follow-up points with a follow-up date. The documentation should be signed by the person performing the inspection. The inspections should be scheduled and assigned to ensure compliance. If you cannot perform these tests yourself, contact us and we can help you.